Fault tracing167Warning messages generated by the control panelWarning Cause What to DoDOWNLOADINGFAILEDDownload function of panel has failed. No datahas been copied from panel to drive.Make sure panel is in local mode.Retry (there might be interference on link).Contact ABB representative.DRIVE ISRUNNINGDOWNLOADINGNOT POSSIBLEDownloading is not possible while motor isrunning.Stop motor. Perform downloading.NOCOMMUNICATION(X)Cabling problem or hardware malfunction onPanel LinkCheck Panel Link connections.Press RESET key. Panel reset may take up tohalf a minute, please wait.(4) = Panel type not compatible with drivecontrol program versionCheck panel type and drive control programversion. Panel type is printed on panel cover.Control program version is stored in parameter33.02.NO FREE IDNUMBERS IDNUMBERSETTING NOTPOSSIBLEPanel Link already includes 31 stations. Disconnect another station from link to free IDnumber.NOT UPLOADEDDOWNLOADINGNOT POSSIBLENo upload function has been performed. Perform upload function before downloading.See chapter Control panel.UPLOADINGFAILEDUpload function of panel has failed. No datahas been copied from drive to panel.Retry (there might be interference on link).Contact ABB representative.WRITE ACCESSDENIEDPARAMETERSETTING NOTPOSSIBLECertain parameters do not allow changes whilemotor is running. If tried, no change isaccepted, and warning is displayed.Stop motor, then change parameter value.Parameter lock is on. Open parameter lock (see parameter 16.02).