Application macros58Default control connectionsThe figure below shows the external control connections for the Tension macro(s).The markings of the terminals on the RMIO board are visible.X201 VREF Reference voltage -10 VDC2 GND 1 kOhm < RL < 10 kOhmX211 VREF Speed Reference 0(2)…10 V1 kOhm < RL < 10 kOhm2 GND3 AI1+ Speed reference 0(2)…10 V, Rin > 200 kOhm4 AI1-5 AI2+ Tension Fdbk Input. 0(4)…20 mA, Rin =100 Ohm6 AI2-7 AI3+ Tension Setpoint. 0(4)…20 mA, Rin = 100Ohm8 AI3-9 AO1+ Output Current 0(4)…20 mA 0…motor nom.current, RL < 700 Ohm10 AO1-11 AO2+ Output Speed 0(4)…20 mA 0…motor nom.speed, RL < 700 Ohm12 AO2-X221 DI1 Stop/Start2 DI2 By default not in use3 DI3 Tension Ctrl Enable.4 DI4 By default not in use5 DI5 Diameter Reset6 DI6 Fault Reset7 +24 V +24 VDC, max. 100 mA8 +24 V9 DGND1 Digital ground10 DGND2 Digital ground11 DIIL Estop InputX231 +24 V Auxiliary voltage output, non-isolated,24 VDC, 250 mA2 GNDX251 RO11Ready2 RO123 RO13X261 RO21Running2 RO223 RO23X271 R031Fault2 R0323 R033==ArpmA