12.3.7.4 Proxy for signals from switching device via GOOSE XLNPROXYGUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1The SwitchType setting controls the evaluation of the operating capability. IfSwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breakeroperating capability, otherwise it is interpreted as a switch operating capability.Table 24:Operating capability values for breaker/switchesValue Breaker operating capability, CbOpCap Switch operating capability, SwOpCap1 None None2 Open Open3 Close – Open Close4 Open – Close – Open Close and Open5 Close – Open – Close – Open Larger values handled as 4, both Close andOpen6 Open – Close – Open – Close – Open7 moretStartMove is the supervision time for the apparatus to start moving after acommand execution is done from the SCSWI function. When the time has expired,the command supervision is reset, and a cause-code is given.During the tIntermediate time, the position indication is allowed to be in anintermediate (00) state. When the time has expired, the command supervision isreset, and a cause-code is given. The indication of the mid-position at SCSWI issuppressed during this time period when the position changes from open to close orvice-versa if the parameter SuppressMidPos is set to On in the SCSWI function.In most cases, the same value can be used for both tStartMove and tIntermediate asin the source function. However, tStartMove may need to be increased toaccommodate for the communication delays, mainly when representing a circuitbreaker.12.4 Logic rotating switch for function selection andLHMI presentation SLGAPC SEMOD114936-1 v512.4.1 IdentificationSEMOD167845-2 v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLogic rotating switch for functionselection and LHMI presentationSLGAPC - -1MRK 505 393-UEN B Section 12ControlLine differential protection RED650 2.2 IEC 267Application manual