Section 16 Metering16.1 Pulse-counter logic PCFCNT IP14600-1 v316.1.1 IdentificationM14879-1 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPulse-counter logic PCFCNTS00947 V1 EN-US-16.1.2 Application M13395-3 v6Pulse-counter logic (PCFCNT) function counts externally generated binary pulses,for instance pulses coming from an external energy meter, for calculation of energyconsumption values. The pulses are captured by the binary input module (BIM),and read by the PCFCNT function. The number of pulses in the counter is thenreported via the station bus to the substation automation system or read via thestation monitoring system as a service value. When using IEC 61850–8–1, a scaledservice value is available over the station bus.The normal use for this function is the counting of energy pulses from externalenergy meters. An optional number of inputs from an arbitrary input module inIED can be used for this purpose with a frequency of up to 40 Hz. The pulse-counter logic PCFCNT can also be used as a general purpose counter.16.1.3 Setting guidelines M13396-4 v9Parameters that can be set individually for each pulse counter from PCM600:• Operation: Off/On• tReporting: 0-3600s• EventMask: NoEvents/ReportEventsConfiguration of inputs and outputs of PCFCNT is made via PCM600.1MRK 505 393-UEN B Section 16MeteringLine differential protection RED650 2.2 IEC 351Application manual