Table 25:Description of the input-output relationshipVALID OPEN CLOSE POSITIONValue Description0 - - 0 Intermediate1 0 0 0 Intermediate1 1 0 1 Open1 0 1 2 Closed1 1 1 3 Bad State12.6.3 Setting guidelines SEMOD55398-5 v5The function does not have any parameters available in the local HMI or PCM600.12.7 Single point generic control 8 signals SPC8GAPCSEMOD176448-1 v312.7.1 IdentificationSEMOD176456-2 v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSingle point generic control 8 signals SPC8GAPC - -12.7.2 Application SEMOD176511-4 v7The Single point generic control 8 signals (SPC8GAPC) function block is acollection of 8 single point commands that can be used for direct commands forexample reset of LED's or putting IED in "ChangeLock" state from remote. In thisway, simple commands can be sent directly to the IED outputs, withoutconfirmation. Confirmation (status) of the result of the commands is supposed tobe achieved by other means, such as binary inputs and SPGAPC function blocks.PSTO is the universal operator place selector for all controlfunctions. Even if PSTO can be configured to allow LOCAL orALL operator positions, the only functional position usable with theSPC8GAPC function block is REMOTE.12.7.3 Setting guidelines SEMOD176518-4 v7The parameters for the single point generic control 8 signals (SPC8GAPC)function are set via the local HMI or PCM600.1MRK 505 393-UEN B Section 12ControlLine differential protection RED650 2.2 IEC 271Application manual