12.2.3 Local remote LOCREM12.2.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote LOCREM - -12.2.3.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are applied viathe function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)function block. A parameter in function block LOCREM is set to choose if the switchsignals are coming from the local HMI or from an external hardware switch connectedvia binary inputs.12.2.3.3 Function blockLOCREMCTRLOFFLOCCTRLREMCTRLLHMICTRLOFFLOCALREMOTEVALIDIEC09000076_1_en.vsdIEC09000076 V1 ENFigure 155: LOCREM function block12.2.3.4 SignalsTable 200:LOCREM Input signalsName Type Default DescriptionCTRLOFF BOOLEAN 0 Disable controlLOCCTRL BOOLEAN 0 Local in controlREMCTRL BOOLEAN 0 Remote in controlLHMICTRL INTEGER 0 LHMI controlTable 201:LOCREM Output signalsName Type DescriptionOFF BOOLEAN Control is disabledLOCAL BOOLEAN Local control is activatedREMOTE BOOLEAN Remote control is activatedVALID BOOLEAN Outputs are validSection 12 1MRK 502 043-UUS BControl336Technical Manual