14.15.2 FunctionalityInsulation liquid monitoring function SSIML (71) is used for monitoring the circuitbreaker condition. Binary information based on the oil level in the circuit breaker isused as input signals to the function. In addition, the function generates alarms basedon received information.14.15.3 Function blockANSI09000128-1-en.vsdSSIML (71)BLOCKBLK_ALMLEVELTEMPLVL_ALMLEVEL_LOSET_L_LOSET_T_LORESET_LOLEVELLVL_ALMLVL_LOTEMPTEMP_ALMTEMP_LOANSI09000128 V1 ENFigure 213: SSIML (71) function block14.15.4 SignalsInputs LEVEL and TEMP together with settings LevelAlmLimit,LevelLOLimit, TempAlarmLimit and TempLOLimit are not supported inthis release of 650 series.14.15.4.1 SSIML InputSignalsTable 357:Input signals for the function block SSIML (LM1-)Signal DescriptionBLOCK Block of functionBLK_ALM Block all the alarmsLEVEL Level input from CBTEMP Temperature of the insulation medium from CBLVL_ALM Level alarm signalLEVEL_LO Level lockout signalSET_L_LO Set level lockoutSET_T_LO Set temperature lockoutRESET_LO Reset level and temperature lockoutSection 14 1MRK 502 043-UUS BMonitoring480Technical Manual