14.19.2 Function blockIEC10000289-1-en.vsdI103ARBLOCK16_ARACT128_CBON130_UNSUIEC10000289 V1 ENFigure 228: I103AR function block14.19.3 SignalsTable 370:I103AR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting16_ARACT BOOLEAN 0 Information number 16, auto-recloser active128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-recloser130_UNSU BOOLEAN 0 Information number 130, unsuccessful reclosing14.19.4 SettingsTable 371:I103AR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)14.20 Function status ground-fault for IEC 60870-5-103I103EF14.20.1 FunctionalityI103EF is a function block with defined functions for ground fault indications inmonitor direction. This block includes the FunctionType parameter, and theinformation number parameter is defined for each output signal.1MRK 502 043-UUS B Section 14Monitoring501Technical Manual