4.1.3 Settings4.1.3.1 Setting parameters for binary input modulesTable 6:BIO_9BI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionBatteryVoltage 24 - 250 V 1 110 Station battery voltageTable 7:BIO_9BI Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionThreshold1 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 1DebounceTime1 0.000 - 0.100 s 0.001 0.005 Debounce time for input 1OscillationCount1 0 - 255 - 1 0 Oscillation count for input 1OscillationTime1 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 1Threshold2 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 2DebounceTime2 0.000 - 0.100 s 0.001 0.005 Debounce time for input 2OscillationCount2 0 - 255 - 1 0 Oscillation count for input 2OscillationTime2 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 2Threshold3 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 3DebounceTime3 0.000 - 0.100 s 0.001 0.005 Debounce time for input 3OscillationCount3 0 - 255 - 1 0 Oscillation count for input 3OscillationTime3 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 3Threshold4 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 4DebounceTime4 0.000 - 0.100 s 0.001 0.005 Debounce time for input 4OscillationCount4 0 - 255 - 1 0 Oscillation count for input 4OscillationTime4 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 4Threshold5 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 5DebounceTime5 0.000 - 0.100 s 0.001 0.005 Debounce time for input 5OscillationCount5 0 - 255 - 1 0 Oscillation count for input 5OscillationTime5 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 5Threshold6 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 6DebounceTime6 0.000 - 0.100 s 0.001 0.005 Debounce time for input 6OscillationCount6 0 - 255 - 1 0 Oscillation count for input 6Table continues on next pageSection 4 1MRK 502 043-UUS BBinary input and output modules50Technical Manual