12.2.3.5 SettingsTable 202:LOCREM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionControlMode Internal LR-switchExternal LR-switch- - Internal LR-switch Control mode for internal/external LR-switch12.2.4 Local remote control LOCREMCTRL12.2.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote control LOCREMCTRL - -12.2.4.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are applied viathe function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)function block. A parameter in function block LOCREM is set to choose if the switchsignals are coming from the local HMI or from an external hardware switch connectedvia binary inputs.12.2.4.3 Function blockIEC09000074_1_en.vsdLOCREMCTRL^PSTO1^PSTO2^PSTO3^PSTO4^PSTO5^PSTO6^PSTO7^PSTO8^PSTO9^PSTO10^PSTO11^PSTO12^HMICTR1^HMICTR2^HMICTR3^HMICTR4^HMICTR5^HMICTR6^HMICTR7^HMICTR8^HMICTR9^HMICTR10^HMICTR11^HMICTR12IEC09000074 V1 ENFigure 156: LOCREMCTRL function block1MRK 502 043-UUS B Section 12Control337Technical Manual