4 Parameter Descriptions4.1 Parameters: 0-** Operation and DisplayParameters related to the fundamental functions of thefrequency converter, function of the LCP keys and configu-ration of the LCP display.4.1.1 0-0* Basic Settings0-01 LanguageOption: Function:[0] * English[10] Chinese0-03 Regional SettingsOption: Function:NOTICEThis parameter cannot be adjusted whilethe motor is running.[0] * Interna-tionalActivates 1-20 Motor Power [kW] for setting themotor power in kW and sets the default valueof 1-23 Motor Frequency to 50 Hz.[1] US Activates 1-20 Motor Power [kW] for setting themotor power in hp and sets the default value of1-23 Motor Frequency to 60 Hz.0-04 Operating State at Power-up (Hand)Option: Function:Selects the operating mode uponreconnection of the frequency converter tomains voltage after power down in Hand(local) operation mode.[0] Resume Restarts the frequency converter, maintainingthe same start/stop settings (applied by[Hand On/Off]) as before the frequencyconverter was powered down.[1] * Forced stop,ref=oldRestarts the frequency converter with a savedlocal reference, after mains voltage reappearsand after pressing [Hand On].[2] Forced stop,ref=0Resets the local reference to 0 uponrestarting the frequency converter.0-06 GridTypeOption: Function:Select the grid type of the supplyvoltage/frequency.NOTICENot all choices are supported inall power sizes.IT grid is a supply mains, where theneutral point of secondary side of thetransformer is not connected toground.Delta is a supply mains where thesecondary part of the transformer isdelta-connected and one phase isconnected to ground.[10] 380-440V/50Hz/IT-grid[11] 380-440V/50Hz/Delta[12] 380-440V/50Hz[20] 440-480V/50Hz/IT-grid[21] 440-480V/50Hz/Delta[22] 440-480V/50Hz[110] 380-440V/60Hz/IT-grid[111] 380-440V/60Hz/Delta[112] 380-440V/60Hz[120] 440-480V/60Hz/IT-grid[121] 440-480V/60Hz/Delta[122] 440-480V/60Hz0-07 Auto DC BrakingOption: Function:Protective function against overvoltage at coast.WARNINGCan cause PWM when coasted.[0] Off Function is not active.[1] * On Function is active.Parameter Descriptions Programming Guide20 Danfoss A/S © Rev. 2014-03-31 All rights reserved. MG06C40244