Logic Action [32] Set dig. out. A low isexecuted.[81] SL DigitalOutput BSee 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [39] Set dig. out. B high is executed.The input goes low whenever the SmartLogic Action [33] Set dig. out. B low isexecuted.[82] SL DigitalOutput CSee 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [40] Set dig. out. C high is executed.The input goes low whenever the SmartLogic Action [34] Set dig. out. C low isexecuted.[83] SL DigitalOutput DSee 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [41] Set dig. out. D high is executed.The input goes low whenever the SmartLogic Action [35] Set dig. out. D low isexecuted.[160] No alarm The output is high when no alarm ispresent.[161] RunningreverseThe output is high when the frequencyconverter is running counterclockwise (thelogical product of the status bits ‘running’AND ‘reverse’).[165] Localreferenceactive[166] Remote refactive[167] StartcommandactivThe output is high when there is an activestart commmand and no stop command isactive.[168] Drive in handmodeThe output is high when the frequencyconverter is in Hand on mode.[169] Drive in automodeThe output is high when the frequencyconverter is in Auto mode.[193] Sleep mode The frequency converter/system hasturned into sleep mode. See parametergroup 22-4* Sleep Mode.[194] Broken belt A broken belt condition has beendetected See parameter group 22-4* SleepMode.5-31 Terminal 29 Digital OutputOption: Function:[0] No operation Functions are described in parameter group5-3* Digital Outputs.5-34 On Delay, Digital OutputRange: Function:0.01 s* [0 - 600 s]5-35 Off Delay, Digital OutputRange: Function:0.01 s* [0 - 600 s]4.6.4 5-4* RelaysParameters for configuring the timing and the outputfunctions for the relays.The parameter is an array parameter representing 2 relays.5-40 Function RelayOption: Function:[0] No operation Default setting for all digital and relayoutputs.[1] Control Ready The control card is ready.[2] Drive ready The frequency converter is ready tooperate. Mains and control suppliesare OK.[3] Drive rdy/rem ctrl The frequency converter is ready foroperation and is in Auto On mode.[4] Stand-by / nowarningReady for operation. No start or stopcommands have been applied. Nowarnings are active.[5] Running The motor is running and a shafttorque is present.[6] Running / nowarningOutput speed is higher than thespeed set in 1-82 Min Speed forFunction at Stop [Hz]. The motor isrunning and no warnings are present.[7] Run in range/nowarnThe motor is running within theprogrammed current ranges set in4-50 Warning Current Low.[8] Run on ref/nowarnMotor runs at reference speed. Nowarnings.[9] Alarm An alarm activates the output. Nowarnings.[10] Alarm or warning An alarm or warning activates theoutput.[11] At torque limit The torque limit set inparameter 4-16 Torque Limit MotorMode or parameter 4-17 Torque LimitGenerator Mode has been exceeded.[12] Out of currentrangeThe motor current is outside therange set in parameter 4-18 CurrentLimit.[13] Below current, low Motor current is lower than set in4-50 Warning Current Low.[14] Above current,highMotor current is higher than set in4-51 Warning Current High.[15] Out of frequencyrangeOutput speed/freqeuncy is outside setin parameter 4-40 Warning Freq. Lowand parameter 4-41 Warning Freq.High.Parameter Descriptions Programming GuideMG06C402 Danfoss A/S © Rev. 2014-03-31 All rights reserved. 534 4