SelectedEventRelayoutputSelectedEventRelayoutputOn DelayP 5-41On DelayP 5-41Off DelayP 5-42130BA171.10Illustration 4.11 On Delay, Relay5-42 Off Delay, RelayArray[2]: Relay1[0], Relay2[1]Range: Function:0.01 s* [0.01 - 600 s] Enter the delay of the relay cut-out time.SelectedEventRelayoutputOn DelayP 5-41Off DelayP 5-42130BA172.10Illustration 4.12 Off Delay, RelayIf the selected event condition changes before the on- oroff delay timer expires, the relay output is unaffected.4.6.5 5-5* Pulse InputThe pulse input parameters are used to define anappropriate window for the impulse reference area byconfiguring the scaling and filter settings for the pulseinputs. Input terminals 29 or 33 act as frequency referenceinputs. Set terminal 29 (5-13 Terminal 29 Digital Input) orterminal 33 (5-15 Terminal 33 Digital Input) to [32] Pulseinput . If terminal 29 is used as an input, then set5-01 Terminal 27 Mode to [0] Input.130BD377.10Ref.Low freq.P 5-50/P 5-55Input(Hz)Highref.valueP 5-53/p 5-58High freq.P 5-51/P 5-56Lowref.valueP 5-52/p 5-57Illustration 4.13 Pulse Input5-50 Term. 29 Low FrequencyRange: Function:4 Hz* [4 - 31999Hz]Enter the low frequency limit correspondingto the low motor shaft speed (i.e. lowreference value) in parameter 5-52 Term. 29Low Ref./Feedb. Value. Refer to the diagramin this section.5-51 Term. 29 High FrequencyRange: Function:32000Hz*[5 - 32000Hz]Enter the high frequency limitcorresponding to the high motor shaftspeed (i.e. high reference value) inparameter 5-53 Term. 29 High Ref./Feedb.Value.5-52 Term. 29 Low Ref./Feedb. ValueRange: Function:0* [-4999 -4999 ]Enter the low reference value limit for the motorshaft speed [Hz]. This is also the lowest feedbackvalue, see also parameter 5-57 Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input(parameter 5-02 Terminal 29 Mode = [0] input and5-13 Terminal 29 Digital Input=applicable value.5-53 Term. 29 High Ref./Feedb. ValueRange: Function:Sizerelated*[-4999 -4999 ]Enter the high reference value [Hz] forthe motor shaft speed and the highfeedback value, see alsoparameter 5-58 Term. 33 High Ref./Feedb.Value. Select terminal 29 as a digitalinput (5-02 Terminal 29 Mode = [0] input(default) and 5-13 Terminal 29 DigitalInput = applicable value).5-55 Term. 33 Low FrequencyRange: Function:4 Hz* [4 - 31999Hz]Enter the low frequency corresponding tothe low motor shaft speed (i.e. lowParameter Descriptions Programming Guide56 Danfoss A/S © Rev. 2014-03-31 All rights reserved. MG06C40244