8-57 Profidrive OFF2 SelectSelect control of the frequency converter OFF2 selection via theterminals (digital input) and/or via the fieldbus. This parameter isactive only when parameter 8-01 Control Site is set to [0] Digitaland ctrl. word and parameter 8-10 Control Word Profile is set to [1]Profidrive profile.Option: Function:[0] Digital input[1] Bus[2] Logic AND[3] * Logic OR8-58 Profidrive OFF3 SelectSelect control of the frequency converter OFF3 selection via theterminals (digital input) and/or via the fieldbus. This parameter isactive only when parameter 8-01 Control Site is set to [0] Digitaland ctrl. word and parameter 8-10 Control Word Profile is set to [1]Profidrive profile.Option: Function:[0] Digital input[1] Bus[2] Logic AND[3] * Logic OR8-79 Protocol Firmware versionRange: Function:Size related* [0 - 65535 ] The version of the protocol firmware.4.9.6 8-8* FC Port DiagnosticsThese parameters are used for monitoring the buscommunication via the FC Port.8-80 Bus Message CountRange: Function:0* [0 - 65536 ] This parameter shows the number of validtelegrams detected on the bus.8-81 Bus Error CountRange: Function:0* [0 - 65536 ] This parameter shows the number of telegramswith faults (e.g. CRC faults), detected on thebus.8-82 Slave Messages RcvdRange: Function:0* [0 - 65536 ] This parameter shows the number of validtelegrams addressed to the slave, sent by thefrequency converter.8-83 Slave Error CountRange: Function:0* [0 - 65536 ] This parameter shows the number of errortelegrams, which could not be executed by thefrequency converter.8-84 Slave Messages SentRange: Function:0* [0 - 65536 ] This parameter shows the number of messagessent from the follower.8-85 Slave Timeout ErrorsRange: Function:0* [0 - 65536 ] This parameter shows the number of followertime-out errors.8-88 Reset FC port DiagnosticsOption: Function:[0] * Do not reset[1] Reset counter4.9.7 8-9* Bus FeedbackUse the parameter group to configure the bus feedback.8-90 Bus Jog 1 SpeedRange: Function:100 RPM* [ 0 - 1500 RPM]8-91 Bus Jog 2 SpeedRange: Function:200 RPM* [ 0 - 1500 RPM]Parameter Descriptions Programming GuideMG06C402 Danfoss A/S © Rev. 2014-03-31 All rights reserved. 734 4