26 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 08Table 2. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Three-Wire SIAC-B – Two andThree Breaker Maintenance Bypass (Continued)Minimum Conductor Size (Phase A, B, and C)Number per PhaseAWG or kcmil(each)1(2)2/0(2)Minimum Conductor Size (Ground)Number per Phase — AWG or kcmil(each)4(1)3(1)Building and Inter-Cabinet GroundMinimum Conductor Size (Ground)Number per Phase—AWG or kcmil(each)4(1)4(1)NOTE Callout letters A and C map to Figure 39, Figure 40, Figure 42, and Figure 43.Table 3. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Three-Wire SIAC-B – Four BreakerMaintenance BypassBasic Unit RatingUnits Rating 60 HzkW 150 200Input/Output Voltage Volts 480/480 480/480AC Input to Maintenance Bypass(3) Phases, (1) GroundAMaximum Amps 218 291Minimum Conductor Size (Phase A, B, and C)Number per PhaseAWG or kcmil(each)2/0(2)4/0(2)Minimum Conductor Size (Ground)Number per Phase — AWG or kcmil(each)4(1)3(1)AC Input to RIB(3) Phases, (1) GroundBMaximum Amps 218 291Minimum Conductor Size (Phase A, B, and C)Number per PhaseAWG or kcmil(each)2/0(2)4/0(2)Minimum Conductor Size (Ground)Number per Phase — AWG or kcmil(each)4(1)3(1)AC Output to Critical LoadFull Load Current(3) Phases, (1) Ground CMaximum Amps 180 240Minimum Conductor Size (Phase A, B, and C)Number per PhaseAWG or kcmil(each)1(2)2/0(2)Minimum Conductor Size (Ground)Number per Phase — AWG or kcmil(each)4(1)3(1)Building and Inter-Cabinet GroundMinimum Conductor Size (Ground)Number per Phase—AWG or kcmil(each)4(1)4(1)NOTE Callout letters A, B and C map to Figure 41 and Figure 44.Installation Plan and Unpacking