68Web page programmingPRC-E Series Instruction Manual MN014003EN August 2015 www.eaton.comThe digital inputs will have green backgrounds with “OFF”text when they are open and a red background with “ON”text when the inputs are closed. In the normal state, therewill be a white filled box beside the status box and yellowfilled if it is overridden.The universal inputs can be configured as digital (dry-contact) inputs or analog (voltage level) inputs except on thePRC750E controller, which has only digital inputs available.If configured as digital inputs, the “Universal In” will havegreen backgrounds with “OFF” text when they are openand a red background with “ON” text when the inputs areclosed. In the normal state, there will be a white filled boxbeside the status box and yellow filled if it is overridden.If configured as analog inputs, the “Analog In” displays thepercentage of the full scale voltage applied to the input.The background color is green in the normal status. In thenormal state, there will be a white filled box beside thestatus box and yellow filled if it is overridden.The “Analog Out” displays the percentage level of theanalog output. In the normal state, there will be a whitefilled box beside the status box and yellow filled if it isoverridden.ControlsControls are logical statements that utilize the inputs tocontrol the groups.otee:N From the Web page, a control can be created tocommand a group only. If another type of pointcontrol is needed, PRC Lighting Optimizationsoftware (PRCLOS) will be required.To create a control, click the “Controls” tab.This opens the “Control” list.Listed are controls created to command internal points,i.e., circuit breakers, groups, outputs, etc.Control configurationThe “Type” refers to the input type.Type options:●● Maintained change●● Reverses group status on input state change●● Maintained normally open●● Group action commanded on input closure andreversed when open●● Maintained normally closed●● Group action commanded when input is open andreversed when closed●● Momentary three-wire●● Two inputs are used, one for the ON command and theother for the OFF command●● Momentary On/Off●● After a momentary closure of input, the state of theoutput will be reversed●● Motion sensorThe “Switch(es)” refers to the input or inputs used tocontrol the action.Switch options:●● DI 1–8●● UI 1–8The “Group” is the commanded group and the action tobe taken. When using the Web page the only availableaction is “On”.Group options:●● GRPA ON, GRPB ON,…GRPP ON