71Web page programmingPRC-E Series Instruction Manual MN014003EN August 2015 www.eaton.comThis screen is populated from the status of the onboard I/Oand buttons of the PRC Digital Switch and the group statusfrom the PRC controller.●● Light level (AO-1)●● Current percentage value of the analog output;this value represents 0 to 10 Vdc output todimming ballasts●● Current setpoint●● % value of the dimming setpoint●● Photo sensor status (AI-1)●● % value of the analog Input; this value represents0 to 10 Vdc from the photocell a●● Motion input 1 status (UI-1)●● On/Off status of the dry-contact switch from themotion sensor a●● Motion input 2 status (DI-1)●● On/Off status of the dry-contact switch from themotion sensor aa ”AI” input of the switch can be programmed to accept analog signal level(AI) or On/Off dry-contact (UI).a ”DI” input can be utilized only for the 2- and 4-button switches; 6-buttonswitch uses the “DI” for the 6th—bottom button.Button configurationClick the “Buttons” tab.This displays the button programming page for DSN.Each button on the switch will have a configuration line.From this Web page, the DSN description, button actions forcontrolled points and button feedback can be programmed.Editing the descriptionClick the “Description” text box.This opens it for edit. Type in the chosen 20-characteralphanumeric description for the switch.Setting the button digital point controlEach button can be individually programmed to controldifferent points or the same point with different dimminglevels. The digital points can be individual circuit breakers,groups of circuit breakers (Flag 1F-16F) or any other digitalpoints used in the controller for logical control statements.Editing the digital pointClick the “Digital Point” drop down arrow of the button tobe programmed.This opens the dropdown list for a quick pick of the internalmotion sensor input enabling and the PRC controllersystem flags, 1F-56F. The MOT_EN1 and MOT_EN2 arecovered under the “Digital Switch Sensors” heading laterin this section.Click the required point to select.To enter an individual circuit breaker point, click the “DigitalPoint” text box of the button to be programmed, this opensthe textbox for edit.