CHAPTER 2 - TECHNICAL DATA3EATON PXG600E User Manual • IM02603003E Rev 5, 11-May-2012 • Firmware Version 5.03:3835Chapter 2 Technical DataTechnical Data SheetMemory Flash 1 GbRAM 128 MbCommunication PortsNetwork PortTwo 10/100 Base T, RJ-45 connectors -See “Connecting a PXG600E tothe Ethernet LAN” on page 16.Configuration Port One USB-B port forconfiguration with a PCSerial Ports• Two RS-485 ports (COM1 andCOM2A) for connection to eitherQCPort or Modbus RTU devices• One RS-232 port (COM2B) for con-nection to Modbus RTU device. (ifused, RS-485 port COM2A will beinactive)• One port for INCOM devicesNetwork Protocols SupportedPort UsedModbus TCP/IP Port 502HTTPS Port 443Web Server/HTTP Port 80SNMPv1 and SNMPv3 Port 161, 162SMTP Port 25BACnet/IP Port 47808DHCPSerial Protocols Supported INCOMQCPortModbus RTUConfiguration Port (USB) Operating System (OS)Supported32 or 64 bit PC-CompatibleScreen Resolution 1280x1024 for best appearanceWeb Browsers Recommended IE 6.0 or higherMozilla Firefox 2.0 or higherNumber of Devices Supported96 Devices Maximum supported between the three portsIndividual port limits:• INCOM port – 64 device limit• COM1 port – 32 device limit, supports either QCPort or Modbus RTU devices• COM2 port – 32 device limit, supports either QCPort or Modbus RTU devicesTherefore, INCOM port + COM1 port + COM2 port cannot exceed 96devicesPower Input Input Voltage, Nominal 24 VDC; 0.8 AInput Voltage Range +/- 20% NominalPower Consumption 8 Watts MaximumOperating Temperature 0 to 60°C (32 to 140°F)Ambient Storage Temperature -40 to 85°C (-40 to 185°F)Relative Humidity 5 to 95% Non-Condensingat 50°C (122°F)Size (H x D x L) 5.3 x 11.4 x 22.6 cm(2.1 x 4.5 x 8.9 in)Weight 0.68 kg (1.5 lb)Regulatory and Standards Compliance• UL 508, Standard forProgrammable Controller Equipment• FCC, Class A, Part 15,Subpart B, Sections 15.107b and 15.109b• EN55022: 1994 Class A, Information Technology Equipment• EN 61000-6-2:2001 Electromagnetic Compatibility (EMC) Party 6-2: Immunityfor Industrial Environments