5-56 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5RxGOOSE Boolean1 EVENTSRange: Disabled, EnabledDefault: DisabledThis setting selects whether Off to On transitions of the RxGOOSE Boolean1 FlexLogic operand are recorded by the eventrecorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are not recorded, even if events areenabled.RxGOOSE DPS inputsNavigate to Settings > Product Setup > Communications > IEC 618560 > GOOSE > RxGOOSE > RxGOOSE DPS Inputs >RxGOOSE DPS1 to access the settings for the first RxGOOSE Boolean. The settings and functionality for the others aresimilar.Figure 5-16: RxGOOSE DPS Inputs panelRxGOOSE DPS1 IDRange: 0 to 12 charactersDefault: RxG DPS1This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. Thefull operand name is the value of this setting appended with "Intermediate," "On," "Off," or "Bad." This descriptive textalso appears in the SCL files associated with the C70.RxGOOSE DPS1 RxGOOSERange: None, RxGOOSE1, RxGOOSE2, and so onDefault: NoneThis setting selects the RxGOOSE containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None,the RxGOOSE DPS1 FlexLogic operand assumes its default state.RxGOOSE DPS1 MemberRange: 1 to 64 in steps of 1Default: 1This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selectsthe first member, 2 selects the second member, and so on. Entering a number greater than the number of members inthe message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operandassuming its default state.