CHAPTER 10: MAINTENANCE BACK UP AND RESTORE SETTINGSC70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 10-31010.2.2 Restore settingsUR device settings can be restored to the values they were at when a URS backup file was created using the EnerVista URSetup software. When the IEC 61850 option is present, the settings can alternatively be to the values they were at when anIID type backup was created either using the EnerVista UR Setup software in online mode or by using any of the supportedfile transfer protocols. Note that TFTP cannot be used here, as TFTP "put" mode is disabled for security reasons.To restore completely, a few settings need to be entered manually either via EnerVista UR Setup or via the UR device frontpanel. If the restore operation is to be via Ethernet, first the UR device must have its IP address settings entered via thefront panel. These are located at SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3) and SETTINGS PRODUCT SETUP COMMUNICATIONS IPv4 ROUTE TABLE 1(6) DEFAULT IPv4 ROUTE GATEWAY ADDRESS.To restore settings from a URS file:1. In EnerVista, connect to the device in the Online Window area.2. Right-click the .urs file in the Offline Window area and select Add Existing Settings File to locate a file, and/or drag-and-drop the file from the Offline Window area to the device in the Online Window area.Figure 10-1: Restoring a URS settings file3. Manually copy the remaining settings, outlined as follows.To restore settings from an IID file using EnerVista software:1. In Windows, make a copy the IID file with a cid extension.2. Connect to the device in the Online Window area.3. In the Offline Window area, right-click Files and select Import Contents From SCD/CID.Figure 10-2: Importing a CID file4. Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URSfile. The URS file is added to the Offline Window area.5. Drag the imported file in the Offline Window to the device in the Online Window.6. Manually copy the remaining settings, outlined as follows.To restore settings from an IID using SFTP:1. In Windows, make a copy the IID file with a cid extension.2. On a computer on the same subnetwork as the UR device, open a SFTP client application, such as WinSCP. Note thatTFTP cannot be used here.3. Use the device's IP address as the host name.