3-42 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALCONNECT TO THE C70 CHAPTER 3: INSTALLATION33.7.3 Automatic discovery of UR devicesThe EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on anEthernet network.Using the Discover button in the Device Setup window, a single click of the mouse triggers the software to detectautomatically any UR-series relays located on the network. The EnerVista UR Setup software then proceeds to configure allsettings and order code options in the window. This feature allows the user to identify and interrogate all UR-series devicesat a location.To discover UR devices:1. In EnerVista, click the Device Setup button.2. In the window that opens, click the Discover button. If the required device is not found, add it manually as outlinedearlier.Figure 3-50: Discover button to detect UR devices in network3.8 Connect to the C70There are four ways to the connect to the device, as follows:• RS232 port (outlined here)• RS485 port• Ethernet port (outlined here)• LANWhen unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for thedevice.3.8.1 Connect to the C70 in EnerVistaFor information on using the EnerVista software, see the Interfaces chapter.To access the relay in EnerVista:1. Open the Settings > Product Setup > Display Properties window as shown. The window opens with a statusindicator on the lower left of the EnerVista UR Setup window.