4-2 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES4• TestingFactory default values are supplied and can be restored after any changes.The following communications settings are not transferred to the C70 with settings files:Modbus Slave AddressModbus TCP Port NumberRS485 COM2 Baud RateRS485 COM2 ParityCOM2 Minimum Response TimeCOM2 SelectionRRTD Slave AddressRRTD Baud RateIP AddressIP Subnet MaskIP RoutingWhen a settings file is loaded to a C70 that is in-service, the following sequence occurs:1. The C70 takes itself out of service.2. The C70 issues a UNIT NOT PROGRAMMED major self-test error.3. The C70 closes the critical fail contact.The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.4.1.3 Event viewingWhile the interface is in either online or offline mode, you can view and analyze data generated by triggered parameters,via one of the following:• Event recorder — The event recorder captures contextual data associated with the last 1024 events, listed inchronological order from most recent to oldest• Oscillography — The oscillography waveform traces and digital states are used to provide a visual display of powersystem and relay operation data captured during specific triggered events4.1.4 File supportThe following support applies, where the Settings List is at the bottom left and the Site List is at the top left of the EnerVistawindow:• Execution — Any EnerVista UR Setup file that is opened launches the application or provides focus to the alreadyopened application. If the file was a settings file (has a .urs extension) that had been removed from the Settings Listnavigation menu, it is added back to the menu.• Drag and Drop — The Site List and Settings List control bar windows are each mutually a drag source and a droptarget for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window andany Windows Explorer directory folder are each mutually a file drag source and drop target.New files that are dropped into the Settings List window are added to the tree, which is automatically sortedalphabetically with respect to settings file names. Files or individual menu items that are dropped in the selecteddevice menu in the Site List window are automatically sent to the online communicating device.4.1.5 EnerVista main windowThe EnerVista UR Setup software window has the following components:1. Title bar that shows the pathname of the active data view or the name of the software2. Main window menu bar3. Main window tool bar