CHAPTER 5: SETTINGS GROUPED ELEMENTSC70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-1695Up to three identical phase current unbalance elements, one per each CT/VT module configured in hardware, are provided. CUR UNBALCE 1 INHNTFACTOR C: 0.0000Range: –0.1000 to 0.1000 in steps of 0.0001 CUR UNBALCE 1 STG 1APICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 2APICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 3APICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 4APICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 1BPICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 2BPICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 3BPICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 4BPICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 1CPICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 2CPICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 3CPICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 4CPICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001 CUR UNBALCE 1 STG 1PKP DELAY: 30.00 sRange: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1 STG 2PKP DELAY: 10.00 sRange: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1 STG 3PKP DELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1 STG 4PKP DELAY: 0.20 sRange: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1DPO DELAY: 0.25 sRange: 0.00 to 600.00 s in steps of 0.01 CUR UNBL 1 BLK STG1:OffRange: FlexLogic operand CUR UNBL 1 BLK STG4:OffRange: FlexLogic operand CUR UNBALCE 1TARGET: Self-ResetRange: Self-reset, Latched, Disabled CUR UNBALCE 1EVENTS: DisabledRange: Disabled, Enabled