5-90 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5XCBR1 SYNCCHECK CLSRange: any FlexLogic operandDefault: ONThis setting is used to select a FlexLogic operand that declares to IEC 61850 services that synchrocheck conditions areacceptable for closing breaker 1. If a SelectWithValue or Operate service with ctlVal true and with Check.SynchroChecktrue is requested of either BkrCSWI1.Pos or Bkr0XCBR1.Pos and the selected operand is not asserted, a NegativeResponse (-Rsp) is issued with the REASON CODE of Blocked-by-synchrocheck.XCBR1 INTERLOCK OPNRange: any FlexLogic operandDefault: ONThis setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are notacceptable for opening breaker 1. While the selected operand is asserted, the value of BkrCILO.EnaOpn.stVal is false. If aSelectWithValue or Operate service with ctlVal false and with Check.Interlock-check true is requested of eitherBkrCSWI1.Pos or Bkr0XCBR1.Pos, and the selected operand is not activated, a Negative Response (-Rsp) is issued withthe REASON CODE of Blocked-by-interlocking.XCBR1 INTERLOCK CLSRange: any FlexLogic operandDefault: ONThis setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are notacceptable for closing breaker 1. While the selected operand is asserted, the value of BkrCILO.EnaCls.stVal is false. If aSelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of eitherBkrCSWI1.Pos or Bkr0XCBR1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with theREASON CODE of Blocked-by-interlocking.XCBR1 Pos ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-enhanced-securityDefault: sbo-with-enhanced-securityThis setting selects the control model clients must use to successfully control the breaker 1 signals markedBkr0XCBR1.PosOpn.ctlVal and Bkr0XCBR1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in theSettings > System Setup section later in this chapter. These signals force a breaker 1 three-phase trip or close controlwhile the operand selected by setting XCBR1 ST.LOC OPERAND is not active."sbo" here is select-before-operate. Enhanced security means that the UR reports to the client the breaker 1 position atthe end of the command sequence.XCBR1 Pos sboTimeoutRange: 2.000 to 60.000 s in steps of 1 sDefault: 30.000 sThis setting specifies the maximum time between a select and an operate command to breaker 1 signals markedBkr0XCBR1.PosOpn.ctlVal and Bkr0XCBR1.PosCls.ctlVal in order for the operand to be successful. This setting is onlyrelevant when XCBR1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.XCBR1 BlkOpn ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the breaker 1 signal markedBkr0XCBR1.BlkOpn.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setupsection later. This signal when true blocks breaker 1 trip control while the operand selected by setting XCBR1 ST.LOCOPERAND is not active.