5-212 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALGROUPED ELEMENTS CHAPTER 5: SETTINGS5Figure 5-107: Neutral directional overcurrent logic5.7.4.5 Neutral current unbalance (ANSI 60N, IEC PVCB/PTOC)SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEUTRAL CURRENT NEUTRAL CURRENTUNBALANCE 1(3) NEUTRAL CURRENT UNBALANCE 1 NTRL CUR UNBALCE 1FUNCTION: DisabledRange: Disabled, Enabled NTRL CUR UNBALCE 1BANK SOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6 NTRL CUR UNBALCE 1K MAG: 0.0000Range: 0.0000 to 0.1500 in steps of 0.0001 NTRL CUR UNBALCE 1K ANG: 0°Range: 0 to 359° in steps of 1 NTRL CUR UNBALCE 1STG 1 PKP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001 NTRL CUR UNBALCE 1STG 1 SLOPE: 2.0%Range: 0.0 to 10.% in steps of 0.1