CHAPTER 5: SETTINGS PRODUCT SETUPC70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-915XCBR1 BlkCls ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the breaker 1 signal markedBkr0XCBR1.BlkCls.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setup sectionlater. This signal when true blocks breaker 1 close control while the operand selected by setting XCBR1 ST.LOC OPERANDis not active.CSWI1 Pos ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-enhanced-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the breaker 1 signals markedBkrCSWI1.PosOpn.ctlVal and BkrCSWI1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings >System Setup section earlier. These signals force a breaker 1 three-phase trip or close control while the operand selectedby setting XCBR1 ST.LOC OPERAND is not active.CSWI1 Pos sboTimeoutRange: 2 to 60 s in steps of 1 sDefault: 30 sThis setting specifies the maximum time between a select and an operate command to breaker 1 via BkrCSWI1.Pos inorder for the operand to be successful. This setting is only relevant when CSWI1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.CSWI1 Pos operTimeoutRange: 0.000 to 2.000 s in steps of 0.001sDefault: 0.100 sThis setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos untilBkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached inthe set time.SwitchesThe UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to accessthe settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoringelement. The settings and functionality for the others are similar.