CHAPTER 5: SETTINGS PRODUCT SETUPC70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-11555.3.9.3 Analog channelsSETTINGS PRODUCT SETUP OSCILLOGRAPHY ANALOG CHANNELSThese settings select the metering actual value recorded in an oscillography trace. The length of each oscillography tracedepends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters availablein a given relay depend on• the type of relay,• the type and number of CT/VT hardware modules installed, and• the type and number of analog input hardware modules installedA list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog Parameters. Theparameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display.It can be time-consuming to scan through the list of parameters via the relay keypad and display — entering this numbervia the relay keypad causes the corresponding parameter to display.All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IBdesignates the IB signal on terminal 2 of the CT/VT module in slot F.If there are no CT/VT modules and analog input modules, no analog traces appear in the file; only the digital traces appear.The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond directlyto the to the 2nd to 25th harmonics in the relay as follows:Analog channel 0 ↔ 2nd harmonicAnalog channel 1 ↔ 3rd harmonic...Analog channel 23 ↔ 25th harmonic5.3.10 Data loggerSETTINGS PRODUCT SETUP DATA LOGGER ANALOG CHANNELS ANALOG CHANNEL 1:OffRange: Off, any FlexAnalog/actual value parameterSee Appendix A for list ANALOG CHANNEL 16:OffRange: Off, any FlexAnalog/actual value parameterSee Appendix A for list DATA LOGGER DATA LOGGER MODE:ContinuousRange: Continuous, Trigger DATA LOGGER TRIGGER:OffRange: FlexLogic operand DATA LOGGER RATE:60000 msecRange: 15 to 3600000 ms in steps of 1 DATA LOGGER CHNL 1:OffRange: Off, any FlexAnalog/actual value parameterSee Appendix A for list DATA LOGGER CHNL 16:OffRange: Off, any FlexAnalog/actual value parameterSee Appendix A for list DATA LOGGER CONFIG:0 CHNL x 0.0 DAYSRange: Not applicable - shows computed data only