5-56 D30 Line Distance Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5An example user display setup and result is shown below:If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on thebottom line only. The units are only displayed on both lines if the units specified both the top and bottom line itemsare different.5.2.15 DIRECT INPUTS/OUTPUTSa) MAIN MENUPATH: SETTINGS PRODUCT SETUP DIRECT I/O USER DISPLAY 1DISP 1 TOP LINE:Current X ~ AShows user-defined text with first tilde marker.MESSAGE DISP 1 BOTTOM LINE:Current Y ~ AShows user-defined text with second tilde marker.MESSAGE DISP 1 ITEM 1:6016Shows decimal form of user-selected Modbus registeraddress, corresponding to first tilde marker.MESSAGE DISP 1 ITEM 2:6357Shows decimal form of user-selected Modbus registeraddress, corresponding to second tilde marker.MESSAGE DISP 1 ITEM 3:0This item is not being used. There is no correspondingtilde marker in top or bottom lines.MESSAGE DISP 1 ITEM 4:0This item is not being used. There is no correspondingtilde marker in top or bottom lines.MESSAGE DISP 1 ITEM 5:0This item is not being used. There is no correspondingtilde marker in top or bottom lines.USER DISPLAYS Current X 0.850Current Y 0.327 AShows the resultant display content. DIRECT I/ODIRECT OUTPUTDEVICE ID: 1Range: 1 to 16MESSAGE DIRECT I/O CH1 RINGCONFIGURATION: YesRange: Yes, NoMESSAGE DIRECT I/O CH2 RINGCONFIGURATION: YesRange: Yes, NoMESSAGE DIRECT I/O DATARATE: 64 kbpsRange: 64 kbps, 128 kbpsMESSAGE DIRECT I/O CHANNELCROSSOVER: DisabledRange: Disabled, EnabledMESSAGE CRC ALARM CH1 See page 5–62.MESSAGE CRC ALARM CH2 See page 5–62.MESSAGE UNRETURNED MESSAGES ALARM CH1 See page 5–63.MESSAGE UNRETURNED MESSAGES ALARM CH2 See page 5–63.NOTE