GE Multilin D30 Line Distance Protection System 8-118 SECURITY 8.2 SETTINGS SECURITY8Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.Figure 8–8: LOCKING FLEXLOGIC ENTRIES THROUGH SETTING TEMPLATESThe FlexLogic™ entries are also shown as locked in the graphical view (as shown below) and on the front panel display.Figure 8–9: SECURED FLEXLOGIC™ IN GRAPHICAL VIEWb) LOCKING FLEXLOGIC™ EQUATIONS TO A SERIAL NUMBERA settings file and associated FlexLogic™ equations can also be locked to a specific UR serial number. Once the desiredFlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specificserial number.1. Select the settings file in the offline window.2. Right-click on the file and select the Edit Settings File Properties item.Typical FlexLogic™ entries without template applied. Typical locked with template viathe command.Template Mode > View In Template ModeFlexLogic™ entries842861A1.CDR