GE Multilin D30 Line Distance Protection System 5-2215 SETTINGS 5.8 INPUTS AND OUTPUTS5Figure 5–121: TELEPROTECTION INPUT/OUTPUT PROCESSING5.8.12 IEC 61850 GOOSE ANALOGSPATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE ANALOGS GOOSE ANALOG INPUT 1(32)The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-seriesdevices. The following settings are available for each GOOSE analog input.• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offlineand the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floatingpoint number. Because of the large range of this setting, not all possible values can be stored. Some values may berounded to the closest possible floating point number.• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE analog input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actualvalues display of the corresponding GOOSE analog input value.• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-log™ values in other D30 features, such as FlexElements™. The base factor is applied to the GOOSE analog inputFlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table. GOOSE ANALOG INPUT 1ANALOG 1 DEFAULT:1000.000Range: –1000000.000 to 1000000.000 in steps of 0.001MESSAGE ANALOG 1 DEFAULTMODE: Default ValueRange: Default Value, Last KnownMESSAGE GOOSE ANALOG 1UNITS:Range: up to 4 alphanumeric charactersMESSAGE GOOSE ANALOG 1 PU:1.000Range: 0.000 to 1000000000.000 in steps of 0.001842750A2.CDRTELEPROT OUTPUT 1-1:(same for 1-2...1-16)TELEPROT INPUT 1-1DEFAULT:(same for 1-2...1-16)Off (Flexlogic Operand)TELEPRO INPUT 1-1 On(same for 1-2...1-16)UR-1(Teleprotection I/O Enabled)Communication channel #1OnOffACTUAL VALUESCHANNEL 1 STATUS:FailOKORSETTINGTELEPROT OUTPUT 1-1:TELEPROT OUTPUT 2-1:(same for 1-2...1-16)Off (Flexlogic Operand)FLEXLOGIC OPERANDTELEPRO INPUT 1-1 OnTELEPRO INPUT 2-1 On(same for 1-2...1-16)UR-2SETTINGSETTINGTELEPROT INPUT 1-1TELEPROT INPUT 2-1DEFAULT:(same for 1-2...1-16)OnOffFailOK ORACTUAL VALUESACTUAL VALUESCHANNEL 1 STATUS:(On 3-terminal system or 2-terminalwith redundant channel)Communication channel #2OnOffACTUAL VALUESCHANNEL 2 STATUS:FailOKORSETTING(same for 2-2...2-16)Off (Flexlogic Operand)FLEXLOGIC OPERAND(same for 2-2...2-16)DEFAULT:(same for 2-2...2-16)OnOffFailOK ORCHANNEL 2 STATUS:UR-2 or UR-3SETTINGSETTINGFLEXLOGIC OPERANDTELEPROT OUTPUT 2-1:(same for 1-2...1-16)TELEPROT INPUT 2-1DEFAULT:(same for 1-2...1-16)Off (Flexlogic Operand)TELEPRO INPUT 2-1 On(same for 1-2...1-16)SETTINGSETTINGFLEXLOGIC OPERAND