6-8 D30 Line Distance Protection System GE Multilin6.2 STATUS 6 ACTUAL VALUES66.2.15 DIRECT DEVICES STATUSPATH: ACTUAL VALUES STATUS DIRECT DEVICES STATUSThese actual values represent the state of direct devices 1 through 16.6.2.16 IEC 61850 GOOSE INTEGERSPATH: ACTUAL VALUES STATUS IEC 61850 GOOSE UINTEGERSThe D30 Line Distance Protection System is provided with optional IEC 61850 communications capability.This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are receivedvia IEC 61850 GOOSE messages sent from other devices.6.2.17 TELEPROTECTION CHANNEL TESTSPATH: ACTUAL VALUES STATUS TELEPROT CH TESTSThe status information for two channels is shown here. DIRECT DEVICES STATUSDIRECT DEVICE 1STATUS: OfflineRange: Offline, OnlineMESSAGE DIRECT DEVICE 2STATUS: OfflineRange: Offline, OnlineMESSAGE DIRECT DEVICE 16STATUS: OfflineRange: Offline, Online IEC 61850 GOOSE UINTEGERSUINT INPUT 10MESSAGE UINT INPUT 20MESSAGE UINT INPUT 160 TELEPROT CH TESTSCHANNEL 1STATUS: n/aRange: n/a, FAIL, OKMESSAGE CHANNEL 1 LOSTPACKETS: 1Range: 1 to 65535 in steps of 1MESSAGE CHANNEL 2STATUS: n/aRange: n/a, FAIL, OKMESSAGE CHANNEL 2 LOSTPACKETS: 1Range: 1 to 65535 in steps of 1MESSAGE VALIDITY OF CHANNELCONFIGURATION: FAILRange: n/a, FAIL, OK