CHAPTER 4: INTERFACES FRONT PANEL INTERFACED30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 4-434User-programmable event-cause indicatorsEvent-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respectivetarget setting selected as “Self-Reset” or “Latched.” If set to “Self-Reset,” then the corresponding event cause LED remainson as long as the operand associated with the element remains asserted. If set to “Latched” and asserted, then it remainson until the operand is reset and then a reset command initiated.All elements that are able to discriminate faulted phases can independently turn on or off the phase A, B, or C LEDs. Thisincludes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operateoperands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.The LEDs have defaults and can be configured to show instead the status of any FlexLogic operand.The labelling area has a clear cover for custom labels. A utility is available to print stick-on labels, as outlined later in thischapter.These LEDs are programmed by default as follows:• PICKUP — LED 6 — Indicates that an element is picked up, and hence a trip can be imminent• VOLTAGE — LED 7 — Indicates voltage was involved• CURRENT — LED 8 — Indicates current was involved• FREQUENCY — LED 9 — Indicates frequency was involved• OTHER — LED 10 — Indicates a composite function was involved• PHASE A — LED 11 — Indicates phase A was involved• PHASE B — LED 12 — Indicates phase B was involved• PHASE C — LED 13 — Indicates phase C was involved• NEUTRAL/GROUND — LED 14 — Indicates that neutral or ground was involved4.2.5 Front panel labelling4.2.5.1 Enhanced front panesThe following procedure requires these pre-requisites:• The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded fromhttp://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed• Small-bladed knifeTo create custom LED and pushbuttons labels for the enhanced front panel:1. Start the EnerVista UR Setup software.2. If not already copied to the Offline Window area, right-click the online device and select the Add Device to OfflineWindow option. Click the Receive button in the window that opens to save the settings file to the Offline Window area.3. Type labels as follows. Select the File > Front Panel Report. The window opens.