5-206 D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUALGROUPED ELEMENTS CHAPTER 5: SETTINGS5configured under the DISTANCE SOURCE. This setting specifies the ratio between the magnitudes of the mutual zero-sequence impedance between the lines and the positive-sequence impedance of the protected line. Set this setting to zeroif the compensation is not to be performed. Note that internally the mutual coupling compensation is applied only if3I_0>1.22*IG to ensure that no mutual coupling compensation is applied when the fault is on the parallel line. Mutualcoupling compensation is applied when distance source is assigned with 8F or 8L type DSP module only and when theratio of the protected line ground current to parallel line ground current is greater than 1.22.GND DIST Z1 ZOM/Z1 ANG — This setting specifies the angle difference between the mutual zero-sequence impedancebetween the lines and the positive-sequence impedance of the protected line.GND DIST Z1 REACH — This setting defines the reach of the zone for the forward and reverse applications. In non-directionalapplications, this setting defines the forward reach of the zone. The reverse reach impedance in non-directionalapplications is set independently. The angle of the reach impedance is entered as the GND DIST Z1 RCA setting. The reachimpedance is entered in secondary ohms.To achieve specified operating speed of distance elements, the relay internally calculates source to line impedance ratio(SIR) from fault phasors. In these calculations, line impedance is estimated based on the zone 1 reach setting. Therefore, inorder to calculate the SIR value properly and to maintain the optimal operating speed of the distance elements, set zone 1reach with a regular 80 to 85% of the line impedance reach setting, even when zone 1 is disabled.GND DIST Z1 RCA — This setting specifies the characteristic angle (similar to the maximum torque angle in previoustechnologies) of the ground distance characteristic for the forward and reverse applications. In the non-directionalapplications, this setting defines the forward reach of the zone. The reverse reach impedance in the non-directionalapplications is set independently. This setting is independent from the GND DIST Z1 DIR RCA setting (the characteristic angleof an extra directional supervising function).GND DIST Z1 REV REACH — This setting defines the reverse reach of the zone set to non-directional (GND DIST Z1 DIR setting).The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to “Forward” or“Reverse.”GND DIST Z1 REV REACH RCA — This setting defines the angle of the reverse reach impedance if the zone is set to non-directional (GND DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or “Reverse.”GND DIST Z1 POL CURRENT — This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and controls the polarizingcurrent used by the reactance comparator of the quadrilateral characteristic. Either the zero-sequence or negative-sequence current can be used. In general, a variety of system conditions must be examined to select an optimumpolarizing current. This setting becomes less relevant when the resistive coverage and zone reach are set conservatively.Also, this setting is more relevant in lower voltage applications such as on distribution lines or cables, as compared withhigh-voltage transmission lines. This setting applies to both the zone 1 and reverse reactance lines if the zone is set to non-directional. See the Application of Settings chapter for additional information.GND DIST Z1 NON-HOMOGEN ANG — This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and provides a methodto correct the angle of the polarizing current of the reactance comparator for non-homogeneity of the zero-sequence ornegative-sequence networks. In general, a variety of system conditions must be examined to select this setting. In manyapplications this angle is used to reduce the reach at high resistances in order to avoid overreaching under far-out reachsettings and/or when the sequence networks are greatly non-homogeneous. This setting applies to both the forward andreverse reactance lines if the zone is set to non-directional. See the Application of Settings chapter for additionalinformation.GND DIST Z1 COMP LIMIT — This setting shapes the operating characteristic. In particular, it enables a lens-shapedcharacteristic of the mho function and a tent-shaped characteristic of the quadrilateral function reactance boundary. Ifthe mho shape is selected, the same limit angle applies to mho and supervising reactance comparators. In conjunctionwith the mho shape selection, this setting improves loadability of the protected line. In conjunction with the quadrilateralcharacteristic, this setting improves security for faults close to the reach point by adjusting the reactance boundary into atent-shape.The relay internally performs zero-sequence compensation for the protected circuit based on the values enteredfor GND DIST Z1 Z0/Z1 MAG and GND DIST Z1 Z0/Z1 ANG, and if configured to do so, zero-sequence compensation formutual coupling based on the values entered for GND DIST Z1 Z0M/Z1 MAG and GND DIST Z1 Z0M/Z1 ANG. As such,enter the GND DIST Z1 REACH and GND DIST Z1 RCA values in terms of positive sequence quantities.