CHAPTER 5: SETTINGS PRODUCT SETUPD30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-335CURRENT PAGERange: Page 1...Page 5Default: Page 1Select the metering page to configure from the drop-down list. There are five pages possible, viewable with the Tabpushbuttons on the graphical front panel.PAGE NAMERange: Page 1...Page 5Default: Page 1Up to 20 characters can be input here as the name of each metering page. The name displays for the Tab pushbutton onthe graphical front panel.LAYOUTRange: 3x4, 4x6, 6x8, 6x4, 8x6, 12x8, 12x4, 16x6, 18x8Default: 6x4This setting determines how many rows and columns display on the graphical front panel with the metering information.The configurable rows in the settings window change dynamically based on this setting.CONTENTRange: Actual, Status, TextDefault: TextSelect the type of content to display.– Actual — an actual value/data. The Configure button becomes active for the actual value to be selected.– Status — one of the operands selected from the STATUS INPUTS fields. Select it in the STATUS INDEX field.– Text — indicates that text is to display instead of a metered valueSTATUS INDEXRange: 1...16Default:This field becomes active when the CONTENT field is set to Status. It selects the input from the STATUS INPUTS to displaythe on/off status of the selected operand.A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.TEXTRange: up to 20 alphanumeric charactersDefault:Enter the text to display on the graphical front panel. This field is active when the CONTENT field is set to Text or Status.When Status is selected, the text displays when the status input is in the "on" state.OFF TEXTRange: up to 20 alphanumeric charactersDefault:Enter the text to display on the graphical front panel when the element being monitored is in an off/closed state. Thisfield is active when the CONTENT field is set to Status. The text displays when the status input is in the "off" state.FONTRange: 16, 18, 20Default: 16Set the font size to display on the graphical front panel.TEXT COLORRange: 24-bit color selectorDefault: BlackSet the text color to display in the specified cell.