CHAPTER 5: SETTINGS PRODUCT SETUPD30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-575Figure 5-18: IEC 61850 protocol panel in EnerVista softwareThe IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and clickan option on the left to display its panel on the right. The following figure shows an example for Server Configuration. TheSETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hoveringthe mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its locationin SCL files.Figure 5-19: IEC 61850 panelOpening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the D30.This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both thosethat are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model(that is, the "private" section). The UR EnerVista Setup software imports all of these settings into the current session, not justthose in the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the currentsession, all other panels for the D30 must be closed before the IEC 61850 panel can be opened, and the software promptsfor this when applicable. Panels for other devices can be open concurrently to facilitate parameter coordination.