CHAPTER 5: SETTINGS PRODUCT SETUPD30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-675Figure 5-27: IEC 61850 TxGOOSE panelA data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottomright of the window.TxGOOSE1 MODERange: Disabled, GOOSE, R-GOOSEDefault: DisabledWhen set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are publishedin IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSEformat according to IEC 61850 90-5, and the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot bechanged.TxGOOSE1 GoCB nameRange: 0 up to 32 VisibleString charactersDefault: GoCB01The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.An ObjectReference to the control block, which consists of the concatenation of the string "/LLN0." and thecontrol block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminateTxGOOSE1 messages from other GOOSE messages. is a syntactic variable that is set to the value of settingMaster functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IEDNAME suffixed with "Master".TxGOOSE1 GoIDRange: 0 to 129 VisibleString charactersDefault: TxGOOSE1The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminatethe TxGOOSE1 messages from other GOOSE messages.