5-10 D30 Line Distance Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5c) REMOTE PASSWORDSThe remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select theSettings > Product Setup > Password Security menu item to open the remote password settings window.Figure 5–2: REMOTE PASSWORD SETTINGS WINDOWProper passwords are required to enable each command or setting level access. A command or setting password consistsof 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-mand or setting password.1. Enter the new password in the Enter New Password field.2. Re-enter the password in the Confirm New Password field.3. Click the Change button. This button will not be active until the new password matches the confirmation password.4. If the original password is not “0”, then enter the original password in the Enter Password field and click the SendPassword to Device button.5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Passwordvalue.If you establish a local connection to the relay (serial), you cannot view remote passcodes.d) ACCESS SUPERVISIONPATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS SUPERVISION ACCESS LEVEL TIMEOUTSMESSAGE INVALID ATTEMPTSBEFORE LOCKOUT: 3Range: 2 to 5 in steps of 1MESSAGE PASSWORD LOCKOUTDURATION: 5 minRange: 5 to 60 minutes in steps of 1NOTE