GE Multilin D30 Line Distance Protection System 5-1315 SETTINGS 5.6 GROUPED ELEMENTS5c) GROUND DISTANCEPATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE GROUND DISTANCE Z1(Z5) GROUND DISTANCE Z1GND DIST Z1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE GND DIST Z1 DIR:ForwardRange: Forward, Reverse, Non-directionalMESSAGE GND DIST Z1SHAPE: MhoRange: Mho, QuadMESSAGE GND DIST Z1Z0/Z1 MAG: 2.70Range: 0.00 to 10.00 in steps of 0.01MESSAGE GND DIST Z1Z0/Z1 ANG: 0°Range: –90 to 90° in steps of 1MESSAGE GND DIST Z1ZOM/Z1 MAG: 0.00Range: 0.00 to 7.00 in steps of 0.01MESSAGE GND DIST Z1ZOM/Z1 ANG: 0°Range: –90 to 90° in steps of 1MESSAGE GND DIST Z1REACH: 2.00 Range: 0.02 to 500.00 ohms in steps of 0.01MESSAGE GND DIST Z1RCA: 85°Range: 30 to 90° in steps of 1MESSAGE GND DIST Z1 REVREACH: 2.00 Range: 0.02 to 500.00 ohms in steps of 0.01MESSAGE GND DIST Z1 REVREACH RCA: 85°Range: 30 to 90° in steps of 1MESSAGE GND DIST Z1 POLCURRENT: Zero-seqRange: Zero-seq, Neg-seqMESSAGE GND DIST Z1 NON-HOMOGEN ANG: 0.0°Range: –40.0 to 40.0° in steps of 0.1MESSAGE GND DIST Z1COMP LIMIT: 90°Range: 30 to 90° in steps of 1MESSAGE GND DIST Z1DIR RCA: 85°Range: 30 to 90° in steps of 1MESSAGE GND DIST Z1DIR COMP LIMIT: 90°Range: 30 to 90° in steps of 1MESSAGE GND DIST Z1 QUADRGT BLD: 10.00 Range: 0.02 to 500.00 ohms in steps of 0.01MESSAGE GND DIST Z1 QUADRGT BLD RCA: 85°Range: 60 to 90° in steps of 1MESSAGE GND DIST Z1 QUADLFT BLD: 10.00 Range: 0.02 to 500.00 ohms in steps of 0.01MESSAGE GND DIST Z1 QUADLFT BLD RCA: 85°Range: 60 to 90° in steps of 1MESSAGE GND DIST Z1SUPV: 0.200 puRange: 0.050 to 30.000 pu in steps of 0.001