5-190 D30 Line Distance Protection System GE Multilin5.7 CONTROL ELEMENTS 5 SETTINGS5SELECTOR 1 FUNCTION: “Enabled” SELECTOR 1 3BIT A0: “CONT IP 1 ON”SELECTOR 1 FULL-RANGE: “4” SELECTOR 1 3BIT A1: “CONT IP 2 ON”SELECTOR 1 STEP-UP MODE: “Time-out” SELECTOR 1 3BIT A2: “CONT IP 3 ON”SELECTOR 1 TIME-OUT: “5.0 s” SELECTOR 1 3BIT MODE: “Time-out”SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON” SELECTOR 1 3BIT ACK: “Off”SELECTOR 1 ACK: “Off” SELECTOR 1 POWER-UP MODE: “Synchronize”Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the followingchanges in the SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS menu:OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCTSETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:PUSHBUTTON 1 FUNCTION: “Self-reset”PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”The logic for the selector switch is shown below:Figure 5–102: SELECTOR SWITCH LOGIC842012A2.CDRstep upacknowledge3-bit position outONFLEXLOGIC™ OPERANDSSELECTOR 1 POS 1SELECTOR 1 POS 2SELECTOR 1 POS 3SELECTOR 1 POS 4SELECTOR 1 POS 5SELECTOR 1 POS 6SELECTOR 1 POS 7SELECTOR 1 STP ALARMSELECTOR 1 BIT ALARMSELECTOR 1 ALARMSELECTOR 1 BIT 0SELECTOR 1 BIT 1SELECTOR 1 BIT 2FLEXLOGIC™ OPERANDSRUNSELECTOR 1 POWER-UP MODE:SETTINGSSELECTOR 1 TIME-OUT:SELECTOR 1 STEP-UP MODE:SELECTOR 1 FULL RANGE:SELECTOR 1 STEP-UP:Off = 0SELECTOR 1 FUNCTION:SETTINGSEnabled = 1SELECTOR 1 ACK:Off = 0SELECTOR 1 3BIT A0:Off = 0SELECTOR 1 3BIT A1:Off = 0SELECTOR 1 3BIT A2:Off = 0SELECTOR 1 3BIT ACK:Off = 0 3-bit acknowledgeSELECTOR 1 POSITIONACTUAL VALUE2134567SELECTOR 1 3BIT MODE:SELECTOR 1 PWR ALARMthree-bit control inputOR