5-38 D30 Line Distance Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know themaximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.The minimum value for all quantities is 0; the maximum values are as follows:• phase current: 46 phase CT primary setting• neutral current: 46 ground CT primary setting• voltage: 275 VT ratio setting• power (real, reactive, and apparent): 46 phase CT primary setting 275 VT ratio setting• frequency: 90 Hz• power factor: 2The GGIO1 status configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO1 STATUS CONFIGURATIONThe NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that areinstantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect untilthe D30 is restarted.The GGIO2 control configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO2 CONTROL CONFIGURATION GGIO2 CF SPSCO 1(64)The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the D30virtual inputs. GGIO1 STATUS CONFIGURATIONNUMBER OF STATUSPOINTS IN GGIO1: 8Range: 8 to 128 in steps of 8MESSAGE GGIO1 INDICATION 1OffRange: FlexLogic operandMESSAGE GGIO1 INDICATION 2OffRange: FlexLogic operandMESSAGE GGIO1 INDICATION 3OffRange: FlexLogic operandMESSAGE GGIO1 INDICATION 128OffRange: FlexLogic operand GGIO2 CF SPCSO 1GGIO2 CF SPCSO 1CTLMODEL: 1Range: 0, 1, or 2