GE Multilin D30 Line Distance Protection System B-27APPENDIX B B.4 MEMORY MAPPINGB41AA Daylight Savings Time (DST) Start Month 0 to 11 --- 1 F237 0 (January)41AB Daylight Savings Time (DST) Start Day 0 to 6 --- 1 F238 0 (Sunday)41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 --- 1 F239 0 (First)41AD Daylight Savings Time (DST) Start Hour 0 to 23 --- 1 F001 241AE Daylight Savings Time (DST) Stop Month 0 to 11 --- 1 F237 0 (January)41AF Daylight Savings Time (DST) Stop Day 0 to 6 --- 1 F238 0 (Sunday)41B0 Daylight Savings Time (DST) Stop Day Instance 0 to 4 --- 1 F239 0 (First)41B1 Daylight Savings Time (DST) Stop Hour 0 to 23 --- 1 F001 2Fault Report Commands (Read/Write Command)41B2 Fault Reports Clear Data Command 0 to 1 --- 1 F126 0 (No)Oscillography (Read/Write Setting)41C0 Oscillography Number of Records 3 to 64 --- 1 F001 1541C1 Oscillography Trigger Mode 0 to 1 --- 1 F118 0 (Auto.Overwrite)41C2 Oscillography Trigger Position 0 to 100 % 1 F001 5041C3 Oscillography Trigger Source 0 to 4294967295 --- 1 F300 041C5 Oscillography AC Input Waveforms 0 to 4 --- 1 F183 2 (16 samples/cycle)41D0 Oscillography Analog Channel n (16 items) 0 to 65535 --- 1 F600 04200 Oscillography Digital Channel n (63 items) 0 to 4294967295 --- 1 F300 0Trip and Alarm LEDs (Read/Write Setting)42B0 Trip LED Input FlexLogic Operand 0 to 4294967295 --- 1 F300 042B2 Alarm LED Input FlexLogic Operand 0 to 4294967295 --- 1 F300 0User Programmable LEDs (Read/Write Setting) (48 modules)42C0 FlexLogic Operand to Activate LED 0 to 4294967295 --- 1 F300 042C2 User LED type (latched or self-resetting) 0 to 1 --- 1 F127 1 (Self-Reset)42C3 ...Repeated for User-Programmable LED 242C6 ...Repeated for User-Programmable LED 342C9 ...Repeated for User-Programmable LED 442CC ...Repeated for User-Programmable LED 542CF ...Repeated for User-Programmable LED 642D2 ...Repeated for User-Programmable LED 742D5 ...Repeated for User-Programmable LED 842D8 ...Repeated for User-Programmable LED 942DB ...Repeated for User-Programmable LED 1042DE ...Repeated for User-Programmable LED 1142E1 ...Repeated for User-Programmable LED 1242E4 ...Repeated for User-Programmable LED 1342E7 ...Repeated for User-Programmable LED 1442EA ...Repeated for User-Programmable LED 1542ED ...Repeated for User-Programmable LED 1642F0 ...Repeated for User-Programmable LED 1742F3 ...Repeated for User-Programmable LED 1842F6 ...Repeated for User-Programmable LED 1942F9 ...Repeated for User-Programmable LED 2042FC ...Repeated for User-Programmable LED 2142FF ...Repeated for User-Programmable LED 224302 ...Repeated for User-Programmable LED 234305 ...Repeated for User-Programmable LED 244308 ...Repeated for User-Programmable LED 25430B ...Repeated for User-Programmable LED 26430E ...Repeated for User-Programmable LED 274311 ...Repeated for User-Programmable LED 284314 ...Repeated for User-Programmable LED 294317 ...Repeated for User-Programmable LED 30Table B–9: MODBUS MEMORY MAP (Sheet 19 of 60)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT