6-2 F650 DIGITAL BAY CONTROLLER GEK-113000-AF6.2 OUT OF SERVICE SETTING CHAPTER 6: COMMISSIONING6.2 Out of service settingThe Relay Out Of Service setting is configured in Setpoint > System Setup > Miscellaneous. The unit also has an Out ofService status that is configured in Relay configuration > Protection elements. When active, these states stop allchanges to PLC equations and functions, including changes to the input/output boards, so if there is a change in any inputor output the unit will not show this change until it has returned to ready mode. For example if an output is closed and theunit goes to the Out of Service state, the output is kept closed even if the state that closed it changes and would otherwiseopen the output. When the unit goes out of the Out of Service state, the output is then opened.When the Out of Service status goes to ON, or the setting has been changed to Enabled, the ready LED also changes tored. Be careful if ready LED is linked to an output, because the output will not change its state. To set outputs to readystate see factory default Logic & Configuration in the detailed manual. Take notice that, in the default configuration, thegeneral setting out of service is enabled, so it is necessary to change to disabled to start working with the unitThe following figure shows the flow chart of these states