5-122 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of groupactivation.5.3.11.6 Event cause LED 1(9)SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS EVENT CAUSE LED 1(9)For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.LED 1 TYPE — If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," theLED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel RESET button, from aremote device via a communications channel, or from any programmed operand.The table outlines default input operand and output operands for each event cause LED.Table 5-16: Default input and output operand for event cause LEDs5.3.12 User-programmable self-testsSETTINGS PRODUCT SETUP USER-PROGRAMMALBE SELF TESTS EVENT CAUSE LED 1 LED 1 OPERAND:LED PICKUPRange: FlexLogic operand LED 1 COLOR:GreenRange: Red, Green, Orange LED 1 TYPE:Self-ResetRange: Self-Reset, LatchedLED Default input operand Output operand Default colorEvent Cause LED 1 LED PICKUP EVENT CAUSE LED 1 GreenEvent Cause LED 2 LED VOLTAGE EVENT CAUSE LED 2 OrangeEvent Cause LED 3 LED CURRENT EVENT CAUSE LED 3 OrangeEvent Cause LED 4 LED FREQUENCY EVENT CAUSE LED 4 OrangeEvent Cause LED 5 LED OTHER EVENT CAUSE LED 5 OrangeEvent Cause LED 6 LED PHASE A EVENT CAUSE LED 6 OrangeEvent Cause LED 7 LED PHASE B EVENT CAUSE LED 7 OrangeEvent Cause LED 8 LED PHASE C EVENT CAUSE LED 8 OrangeEvent Cause LED 9 LED NEUTRAL/GROUND EVENT CAUSE LED 9 Orange USER-PROGRAMMABLE SELF TESTS DIRECT RING BREAKFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equippedwith Direct Input/Output module. DIRECT DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equippedwith Direct Input/Output module. RxGOOSE OFFFUNCTION: EnabledRange: Disabled, Enabled FIRST ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled SEC. ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled THIRD ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled SFP MODULE FAILFUNCTION: DisabledRange: Disabled, Enabled BATTERY FAILFUNCTION: EnabledRange: Disabled, Enabled