CHAPTER 5: SETTINGS PRODUCT SETUPG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-1235All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.This settings menu allows enabling and disabling of most minor self-test alarms.When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display targetmessages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7for information on major and minor self-test alarms.When using the graphical front panel and setting annunciator alarms, the function needs to be enabled here too, else thealarm is not triggered.5.3.13 Control pushbuttonsSETTINGS PRODUCT SETUP CONTROL PUSHBUTTONS CONTROL PUSHBUTTON 1(7)This feature is supported with enhanced and standard front panels.There are three standard control pushbuttons, labelled USER 1, USER 2, and USER 3, on the standard and enhanced frontpanels. These are user-programmable and can be used for various applications such as performing an LED test, switchingsetting groups, and invoking and scrolling though user-programmable displays.The location of the control pushbuttons are shown in the following figures.Figure 5-51: Control pushbuttons (enhanced front panel)An additional four control pushbuttons are included on the standard front panel when the G30 is ordered with the 12 user-programmable pushbutton option. SNTP FAILFUNCTION: EnabledRange: Disabled, Enabled IRIG-B FAILFUNCTION: EnabledRange: Disabled, Enabled PTP FAILFUNCTION: EnabledRange: Disabled, Enabled CONTROL PUSHBUTTON 1 CONTROL PUSHBUTTN 1 IDCTRL PB 1Range: up to 20 alphanumeric characters CONTROL PUSHBUTTON 1FUNCTION: DisabledRange: Disabled, Enabled CONTROL PUSHBUTTON 1EVENTS: DisabledRange: Disabled, Enabled