CHAPTER 5: SETTINGS FLEXLOGICG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-1795ELEMENT:Breaker controlBREAKER 1 OFF CMDBREAKER 1 ON CMDBREAKER 1 ΦA BAD STBREAKER 1 ΦA INTERMBREAKER 1 ΦA CLSDBREAKER 1 ΦA OPENBREAKER 1 ΦB BAD STBREAKER 1 ΦB INTERMBREAKER 1 ΦB CLSDBREAKER 1 ΦB OPENBREAKER 1 ΦC BAD STBREAKER 1 ΦC INTERMBREAKER 1 ΦC CLSDBREAKER 1 ΦC OPENBREAKER 1 BAD STATUSBREAKER 1 CLOSEDBREAKER 1 OPENBREAKER 1 DISCREPBREAKER 1 TROUBLEBREAKER 1 MNL OPENBREAKER 1 MNL CLSBREAKER 1 TRIP ABREAKER 1 TRIP BBREAKER 1 TRIP CBREAKER 1 ANY P OPENBREAKER 1 ONE P OPENBREAKER 1 OOSBREAKER 1 TAG ONBREAKER 1 TAG OFFBREAKER 1 SUBD CLSDBREAKER 1 SUBD OPENBREAKER 1 BYPASS ONBREAKER 1 BYPASS OFFBREAKER 1 BLK RCLSBREAKER 1 ENA RCLSBreaker 1 3-pole open command/trip initiatedBreaker 1 close command initiatedBreaker 1 phase A bad status is detected (discrepancy between the 52/a and52/b contacts)Breaker 1 phase A intermediate status is detected (transition from oneposition to another)Breaker 1 phase A is closedBreaker 1 phase A is openBreaker 1 phase B bad status is detected (discrepancy between the 52/a and52/b contacts)Breaker 1 phase B intermediate status is detected (transition from oneposition to another)Breaker 1 phase B is closedBreaker 1 phase B is openBreaker 1 phase C bad status is detected (discrepancy between the 52/a and52/b contacts)Breaker 1 phase C intermediate status is detected (transition from oneposition to another)Breaker 1 phase C is closedBreaker 1 phase C is openBreaker 1 bad status is detected on any poleBreaker 1 is closedBreaker 1 is openBreaker 1 has discrepancyBreaker 1 trouble alarmBreaker 1 manual openBreaker 1 manual closeBreaker 1 trip phase A commandBreaker 1 trip phase B commandBreaker 1 trip phase C commandAt least one pole of breaker 1 is openOnly one pole of breaker 1 is openBreaker 1 is out of serviceBreaker 1 tagged so manual trip and close and autoreclose are blockedBreaker 1 not taggedBreaker 1 status manually substituted to closedBreaker 1 status manually substituted to openBreaker 1 control interlocking is manually bypassedBreaker 1 control interlocking is not manually bypassedBreaker 1 command to manually block autorecloseBreaker 1 command to manually enable autorecloseBREAKER 2 Same set of operands as shown for BREAKER 1ELEMENT:CT failCT FAIL 1 PKPCT FAIL 1 OPCT fail has picked upCT fail has dropped outCT FAIL 2 to 4 Same set of operands as per CT FAIL 1ELEMENT:Digital countersCounter 1 HICounter 1 EQLCounter 1 LODigital counter 1 output is ‘more than’ comparison valueDigital counter 1 output is ‘equal to’ comparison valueDigital counter 1 output is ‘less than’ comparison valueCounter 2 to 8 Same set of operands as shown for Counter 1ELEMENT:Digital elementsDig Element 1 PKPDig Element 1 OPDig Element 1 DPODigital Element 1 is picked upDigital Element 1 is operatedDigital Element 1 is dropped outDig Element 2 to 48 Same set of operands as shown for Dig Element 1ELEMENT:Sensitive directionalpowerDIR POWER 1 STG1 PKPDIR POWER 1 STG2 PKPDIR POWER 1 STG1 DPODIR POWER 1 STG2 DPODIR POWER 1 STG1 OPDIR POWER 1 STG2 OPDIR POWER 1 PKPDIR POWER 1 DPODIR POWER 1 OPStage 1 of the directional power element 1 has picked upStage 2 of the directional power element 1 has picked upStage 1 of the directional power element 1 has dropped outStage 2 of the directional power element 1 has dropped outStage 1 of the directional power element 1 has operatedStage 2 of the directional power element 1 has operatedThe directional power element has picked upThe directional power element has dropped outThe directional power element has operatedDIR POWER 2 Same set of operands as DIR POWER 1Operand type Operand syntax Operand description