CHAPTER 6: ACTUAL VALUES STATUSG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-766.3.8 RxGOOSE statusACTUAL VALUES STATUS RxGOOSE STATUSThe All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSEInput.6.3.9 RxGOOSE statisticsACTUAL VALUES STATUS RxGOOSE STATISTICS RxGOOSE 1(64)stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNumeach time that the state of one or more of the GOOSE message members is sent with a revised value.sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNumto zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments itwhenever a GOOSE message is resent without any member value change.IGMP — Multicast (SSM and ASM) modes of R-GOOSE reception require that the G30 device subscribe to a multicast groupover the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMPnegotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP isconfigured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and thereforecommunication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configuredfor SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.6.3.10 Digital countersACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8) RxGOOSE STATUS All RxGOOSE Online:YesRange: Yes, No RxGOOSE 1 Status:OfflineRange: Online, Offline RxGOOSE 64 Status:OfflineRange: Online, OfflineThe G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at thetime of ordering. See the Order Codes section of chapter 2 for details. RxGOOSE 1 RxGOOSE 1stNum: 0Range: 0 up to 4,294,967,295 RxGOOSE 1sqNum: 0Range: 0 up to 4,294,967,295 R-RxGOOSE 1IGMP: OffRange: On, OffThe G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at thetime of ordering. See the Order Codes section of chapter 2 for details. DIGITAL COUNTERS Counter 1 Counter 1 ACCUM:0 Counter 1 FROZEN:0