CHAPTER 8: APPLICATION OF SETTINGS SETTINGSG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 8-788.2.2 Power systemAlways enable frequency tracking for generator applications. Make the following power system parameters changes in theEnerVista software or the front panel SETTINGS SYSTEM SETUP POWER SYSTEM VOLTAGE BANK F5 menu.8.2.3 Signal sourcesTwo sources are required for this application example. The “LINE” source uses the phase and auxiliary VT inputs and the CTinput wired to the generator output CT. The “GEN” source uses the phase VT inputs and the CT input wired to the generatorneutral CT. Including the phase VT inputs for both sources allows the user to choose the location of elements that use bothvoltage and current. Elements using the auxiliary VT input are assigned to the “GEN” source.Make the following changes through the EnerVista software or the front panel SETTINGS SYSTEM SETUP SOURCE 1and SETTINGS SYSTEM SETUP SOURCE 2 menus.