6-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALMETERING CHAPTER 6: ACTUAL VALUES6The daily rate loss of life is summarized at 00:00 h, and displayed for the next 24 hour period. The transformeraccumulated loss of life in hours is also available. It can be reset by either changing the XFMR INITIAL LOSS OF LIFE setting orthrough the COMMANDS CLEAR RECORDS CLEAR LOSS OF LIFE RECORDS command.6.4.3 Sources6.4.3.1 MenuACTUAL VALUES METERING SOURCE SRC 1This menu displays the metered values available for each source.Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignmentsfor this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and powervalues are unavailable.6.4.3.2 Phase current meteringACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT SOURCE SRC 1 PHASE CURRENT SRC 1See below GROUND CURRENT SRC 1See page 6-19 PHASE VOLTAGE SRC 1See page 6-19 AUXILIARY VOLTAGE SRC 1See page 6-20 POWER SRC 1See page 6-20 ENERGY SRC 1See page 6-21 FREQUENCY SRC 1See page 6-21 CURRENT HARMONICS SRC 1See page 6-22 VOLTAGE HARMONICS SRC 1See page 6-22 PHASE CURRENT SRC 1 SRC 1 RMS Ia: 0.000b: 0.000 c: 0.000 A SRC 1 RMS Ia:0.000 A SRC 1 RMS Ib:0.000 A SRC 1 RMS Ic:0.000 A SRC 1 RMS In:0.000 A SRC 1 PHASOR Ia:0.000 A 0.0° SRC 1 PHASOR Ib:0.000 A 0.0°