GE Multilin G60 Generator Management Relay 5-235 SETTINGS 5.2 PRODUCT SETUP5The GGIO1 status configuration points are shown below:PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO1 STATUS CONFIGURATIONThe NUMBER OF STATUS POINTS IN GGIO1 setting determines the number of “Ind” (single point status indications) that areinstantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect untilthe G60 is restarted.The GGIO2 control configuration points are shown below:PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ GGIO2 CONTROL... Ö GGIO2 CF SPSCO 1(64)The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the G60virtual inputs.The GGIO4 analog configuration points are shown below:PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850... ÖØ GGIO4 ANALOG CONFIGURATIONThe NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value ischanged, the G60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newlyconfigured number of analog points. GGIO1 STATUS CONFIGURATIONNUMBER OF STATUSPOINTS IN GGIO1: 8Range: 8 to 128 in steps of 8MESSAGE GGIO1 INDICATION 1OffRange: FlexLogic™ operandMESSAGE GGIO1 INDICATION 2OffRange: FlexLogic™ operand↓MESSAGE GGIO1 INDICATION 128OffRange: FlexLogic™ operand GGIO2 CF SPCSO 1GGIO2 CF SPCSO 1CTLMODEL: 1Range: 0, 1, 2 GGIO4 ANALOG CONFIGURATIONNUMBER OF ANALOGPOINTS IN GGIO4: 8Range: 4 to 32 in steps of 4MESSAGE GGIO4 ANALOG 1 MEASURED VALUEMESSAGE GGIO4 ANALOG 2 MEASURED VALUE↓MESSAGE GGIO4 ANALOG 32 MEASURED VALUE