C-4 G60 Generator Management Relay GE MultilinC.2 SERVER DATA ORGANIZATION APPENDIX CC• PTUV: phase undervoltage, auxiliary undervoltage, third harmonic neutral undervoltage• PTOV: phase overvoltage, neutral overvoltage, auxiliary overvoltage, negative sequence overvoltage• RBRF: breaker failure• RREC: autoreclosure• RPSB: power swing detection• RFLO: fault locator• XCBR: breaker controlThe protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 isPIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the G60 protection elements, these flagstake their values from the pickup and operate FlexLogic™ operands for the corresponding element.Some protection elements listed above contain directional start values. For example, the directional start value for PDIS1 isPDIS1.ST.Str.dirGeneral. This value is built from the directional FlexLogic™ operands for the element.The RFLO logical node contains the measurement of the distance to fault calculation in kilometers. This value originates inthe fault locator function.The XCBR logical node is directly associated with the breaker control feature.• XCBR1.ST.Loc: This is the state of the XCBR1 local/remote switch. A setting is provided to assign a FlexLogic™ oper-and to determine the state. When local mode is true, IEC 61850 client commands will be rejected.• XCBR1.ST.Opcnt: This is an operation counter as defined in IEC 61850. Command settings are provided to allow thecounter to be cleared.• XCBR1.ST.Pos: This is the position of the breaker. The breaker control FlexLogic™ operands are used to determinethis state. If the breaker control logic indicates that the breaker, or any single pole of the breaker, is closed, then thebreaker position state is “on”. If the breaker control logic indicates that the breaker is open, then the breaker positionstate is “off”.• XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker open commands from IEC61850 clients will be rejected.• XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker close commands from IEC61850 clients will be rejected.• XCBR1.CO.Pos: This is where IEC 61850 clients can issue open or close commands to the breaker. SBO control withnormal security is the only supported IEC 61850 control model.• XCBR1.CO.BlkOpn: This is where IEC 61850 clients can issue block open commands to the breaker. Direct controlwith normal security is the only supported IEC 61850 control model.• XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct controlwith normal security is the only supported IEC 61850 control model.